Violation Detail
Standard Cited: 19100119 D03 II Process safety management of highly hazardous chemicals.
Inspection Nr: 1727664.015
Citation: 01002A
Citation Type: Other
Abatement Status: Abatement Completed
Initial Penalty: $16,131.00
Current Penalty: $8,529.00
Issuance Date: 06/07/2024
Nr Instances: 1
Nr Exposed: 3
Abatement Date: 08/05/2024
Gravity: 10
Report ID: 0625400
Contest Date:
Final Order: 07/05/2024
Related Event Code (REC):
Emphasis:
Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
---|---|---|---|---|---|---|
Penalty | I: Informal Settlement | 07/05/2024 | $8,529.00 | 08/05/2024 | Other | |
Penalty | Z: Issued | 06/07/2024 | $16,131.00 | 07/26/2024 | Serious |
Text For Citation: 01 Item/Group: 002A Hazard:
29 CFR 1910.119(d)(3)(ii): The employer did not document that equipment complies with recognized and generally accepted good engineering practices: (a) On February 13, 2024, and at times prior thereto, at the Ajinomoto facility located in Lampasas, Texas, the employer did not ensure that the low temperature recirculator vessel complies with recognized and generally good acceptable practices such as, but not limited to, ASME Section VIII Div. 1, UCS-160 Vessels operating at temperatures colder than the MDMT stamped on the nameplate, when the employer operated the low temperature recirculator below the manufacturer-defined limits of the minimum design metal temperature for the vessel.