Violation Detail
Standard Cited: 19100119 J02 Process safety management of highly hazardous chemicals.
Inspection Nr: 1678654.015
Citation: 01002A
Citation Type: Serious
Abatement Status: Abatement Completed
Initial Penalty: $12,278.00
Current Penalty: $8,000.00
Issuance Date: 12/14/2023
Nr Instances: 1
Nr Exposed: 900
Abatement Date: 02/12/2024
Gravity: 5
Report ID: 0521400
Contest Date:
Final Order: 01/09/2024
Related Event Code (REC):
Emphasis:
Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
---|---|---|---|---|---|---|
Penalty | I: Informal Settlement | 01/09/2024 | $8,000.00 | 02/12/2024 | Serious | |
Penalty | Z: Issued | 12/14/2023 | $12,278.00 | 01/22/2024 | Serious |
Text For Citation: 01 Item/Group: 002A Hazard:
29 CFR 1910.119(j)(2):The employer did not establish or implement written procedures to maintain the on-going integrity of process equipment: (a) Piping throughout the facility - On or about June 22, 2023, the employer did not establish a mechanical integrity program or procedure to address Corrosion Under Insulation of the ammonia refrigeration piping system. Employees performing tasks in adjacent production areas would be exposed to ammonia vapors in the event of a significant release. Abatement certification is required for this item in accordance with the requirements of 29 CFR 1903.19(c).