Violation Detail
Standard Cited: 19100107 B05 I Spray finishing using flammable and combustible materials.
Inspection Nr: 1650317.015
Citation: 01002A
Citation Type: Serious
Abatement Status: Abatement Completed
Initial Penalty: $10,938.00
Current Penalty: $10,938.00
Issuance Date: 08/09/2023
Nr Instances: 1
Nr Exposed: 65
Abatement Date: 01/02/2024
Gravity: 10
Report ID: 0111400
Contest Date:
Final Order: 09/01/2023
Related Event Code (REC): C
Emphasis:
Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
---|---|---|---|---|---|---|
Penalty | I: Informal Settlement | 09/01/2023 | $10,938.00 | 01/02/2024 | Serious | |
Penalty | Z: Issued | 08/09/2023 | $10,938.00 | 09/28/2023 | Serious |
Text For Citation: 01 Item/Group: 002A Hazard:
29 CFR 1910.107(b)(5)(i): The average air speed over the open face of the paint spray booth was less than 100 linear feet per minute and there were no visible gauges, audible alarms or pressure activated devices installed in paint spray booth to indicate or insure that the required air speed was maintained: Production Area: 1) The average air speed over the open face of both the Front Shell Booth and the Roof Booth was less than 100 linear feet per minute; 2) Both the Front Shell Booth and the Roof Booth Booth were lacking visible gauges, audible alarms , or pressure-activated devices that would indicate or insure that the required air velocity in each booth was being maintained.