Violation Detail
Standard Cited: 19260152 C04 I Flammable liquids.
Inspection Nr: 1644320.015
Citation: 01002A
Citation Type: Other
Abatement Status: Abatement Completed
Initial Penalty: $15,625.00
Current Penalty: $15,625.00
Issuance Date: 06/01/2023
Nr Instances: 1
Nr Exposed: 5
Abatement Date: 06/13/2023
Gravity: 10
Report ID: 0420100
Contest Date:
Final Order: 06/23/2023
Related Event Code (REC):
Emphasis:
Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
---|---|---|---|---|---|---|
Penalty | I: Informal Settlement | 06/23/2023 | $15,625.00 | 06/13/2023 | Other | |
Penalty | Z: Issued | 06/01/2023 | $15,625.00 | 06/13/2023 | Serious |
Text For Citation: 01 Item/Group: 002A Hazard:
29 CFR 1926.152(c)(4)(i): Portable outdoor storage tank for flammable or combustible liquids was nearer than 20 feet from the building: (a) Texas Road House Construction Site, Fort Campbell, KY - East side of building exterior: On or about 1/18/2023, and at times prior, the employer exposed employees to fire and explosive hazards, in that a 480 gallon, portable, outdoor fuel storage tank was placed 2.8 feet from the building while employees were working in close proximity to the unit.