Violation Detail
Standard Cited: 19260403 I02 II General requirements.
Inspection Nr: 1514582.015
Citation: 01002A
Citation Type: Serious
Abatement Status: Corrected During Inspection
Initial Penalty: $10,513.00
Current Penalty: $5,256.50
Issuance Date: 05/24/2021
Nr Instances: 1
Nr Exposed: 2
Abatement Date:
Gravity: 10
Report ID: 0522000
Contest Date:
Final Order: 06/21/2021
Related Event Code (REC): C
Emphasis:
Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
---|---|---|---|---|---|---|
Penalty | I: Informal Settlement | 06/21/2021 | $5,256.50 | Serious | ||
Penalty | Z: Issued | 05/24/2021 | $10,513.00 | Serious |
Text For Citation: 01 Item/Group: 002A Hazard:
29 CFR 1926.403(i)(2)(ii):In locations where electric equipment operating at 600 volts, nominal, or less is exposed to physical damage, enclosures or guards were not so arranged and of such strength as to prevent such damage: Located in the central area of the basement adjacent to the elevator shaft there was an observed energized 400 volt breaker panel cabinet without the face or trim cover to effectively close the breaker panel exposing employees to the lack of adequately guarding live parts, in that the face panel opening and interior uninsulated energized lugs and wiring were covered or partially with cardboard which was not so arranged and of such strength as to prevent physical damage.