Violation Detail
Standard Cited: 19100303 B02 General.
Inspection Nr: 1375969.015
Citation: 01002A
Citation Type: Serious
Abatement Status: Quick Fix
Initial Penalty: $3,441.00
Current Penalty: $2,500.00
Issuance Date: 02/03/2020
Nr Instances: 1
Nr Exposed: 2
Abatement Date:
Gravity: 5
Report ID: 0112000
Contest Date:
Final Order: 03/10/2020
Related Event Code (REC):
Emphasis:
| Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
|---|---|---|---|---|---|---|
| Penalty | I: Informal Settlement | 03/10/2020 | $2,500.00 | Serious | ||
| Penalty | Z: Issued | 02/03/2020 | $3,441.00 | Serious |
Text For Citation: 01 Item/Group: 002A Hazard:
29 CFR 1910.303(b)(2): Listed or labeled electrical equipment was not used or installed in accordance with instructions included in the listing or labeling: Laundry: On, or about, December 16, 2019, a two wire fan was used in the exhaust duct for the dryer. The fan was not provided with an equipment grounding conductor.
Translate