Violation Detail
Standard Cited: 19100333 C03 I A Selection and use of work practices
Inspection Nr: 1222891.015
Citation: 01002A
Citation Type: Serious
Abatement Status: Not Completed - Worksite Changed
Initial Penalty: $12,675.00
Current Penalty: $12,675.00
Issuance Date: 05/30/2017
Nr Instances: 1
Nr Exposed: 1
Abatement Date: 06/27/2017
Gravity: 10
Report ID: 0636900
Contest Date:
Final Order: 07/31/2017
Related Event Code (REC): A
Emphasis:
| Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
|---|---|---|---|---|---|---|
| Penalty | Z: Issued | 05/30/2017 | $12,675.00 | 06/27/2017 | Serious |
Text For Citation: 01 Item/Group: 002A Hazard:
29 CFR 1910.333(c)(3)(i)(A): When an unqualified person is working in an elevated position near overhead lines, the location shall be such that the person and the longest conductive object he or she may contact cannot come closer to any unguarded, energized overhead line than the following distances: (1) For voltages to ground 50kV or below - 10 feet (305 cm); (2) For voltages to ground over 50kV - 10 feet (305 cm) plus 4 inches (10 cm) for every 10kV over 50kV. At the jobsite, an employee performing tree trimming activities and the employer did not ensure that unqualified personnel working in an elevated position and the longest conductive objects maintained the required distances from any unguarded, energized overhead power line exposing the employee to electric shock, severe burns and electrocution.
Translate