Powered by GoogleTranslate

Violation Detail

Standard Cited: 19100303 F02 General.

Inspection Nr: 1087185.015

Citation: 01002A

Citation Type: Serious

Abatement Status: Abatement Completed

Initial Penalty: $7,000.00

Current Penalty: $12,675.00

Issuance Date: 02/18/2016

Nr Instances: 1

Nr Exposed: 6

Abatement Date: 06/21/2017

Gravity: 10

Report ID: 0213100

Contest Date: 03/10/2016

Final Order: 06/19/2017

Related Event Code (REC): C

Emphasis:


Penalty and Failure to Abate Event History
Type Latest Event Event Date Penalty Abatement Due Date Citation Type Failure to Abate Inspection
Penalty F: Formal Settlement 06/19/2017 $12,675.00 06/21/2017 Serious  
Penalty C: Contested 03/11/2016 $7,000.00 02/22/2016 Serious  
Penalty Z: Issued 02/18/2016 $7,000.00 02/22/2016 Serious  

Text For Citation: 01 Item/Group: 002A Hazard:

29 CFR 1910.303(f)(2): Each service, feeder, and branch circuit, at its disconnecting means or overcurrent device, was not legibly marked to indicate its purpose, nor located and arranged so the purpose was evident: a) Campsite- On or about August 25, 2015 and December 4, 2015, 120 Volt, 30 amp breaker field boxes throughout the campsite were not adequately labeled. The breakers in the field boxes were not labeled to indicate the correct and corresponding campsite box. The breakers in the field boxes must be properly labeled to ensure employees can turn off the power to the correct and corresponding campsite box to safely perform any servicing or maintenance operations on that campsite box, and avoid electrical hazards.

Thank You for Visiting Our Website

You are exiting the Department of Labor's Web server.

The Department of Labor does not endorse, takes no responsibility for, and exercises no control over the linked organization or its views, or contents, nor does it vouch for the accuracy or accessibility of the information contained on the destination server. The Department of Labor also cannot authorize the use of copyrighted materials contained in linked Web sites. Users must request such authorization from the sponsor of the linked Web site. Thank you for visiting our site. Please click the button below to continue.