Violation Detail
Standard Cited: 19100303 F02 General.
Inspection Nr: 1087185.015
Citation: 01002A
Citation Type: Serious
Abatement Status: Abatement Completed
Initial Penalty: $7,000.00
Current Penalty: $12,675.00
Issuance Date: 02/18/2016
Nr Instances: 1
Nr Exposed: 6
Abatement Date: 06/21/2017
Gravity: 10
Report ID: 0213100
Contest Date: 03/10/2016
Final Order: 06/19/2017
Related Event Code (REC): C
Emphasis:
Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
---|---|---|---|---|---|---|
Penalty | F: Formal Settlement | 06/19/2017 | $12,675.00 | 06/21/2017 | Serious | |
Penalty | C: Contested | 03/11/2016 | $7,000.00 | 02/22/2016 | Serious | |
Penalty | Z: Issued | 02/18/2016 | $7,000.00 | 02/22/2016 | Serious |
Text For Citation: 01 Item/Group: 002A Hazard:
29 CFR 1910.303(f)(2): Each service, feeder, and branch circuit, at its disconnecting means or overcurrent device, was not legibly marked to indicate its purpose, nor located and arranged so the purpose was evident: a) Campsite- On or about August 25, 2015 and December 4, 2015, 120 Volt, 30 amp breaker field boxes throughout the campsite were not adequately labeled. The breakers in the field boxes were not labeled to indicate the correct and corresponding campsite box. The breakers in the field boxes must be properly labeled to ensure employees can turn off the power to the correct and corresponding campsite box to safely perform any servicing or maintenance operations on that campsite box, and avoid electrical hazards.