Violation Detail
Standard Cited: 19100305 G01 IV A Wiring methods, components, and equipment for general use.
Inspection Nr: 1051982.015
Citation: 01002A
Citation Type: Serious
Abatement Status: Abatement Completed
Initial Penalty: $5,390.00
Current Penalty: $5,390.00
Issuance Date: 08/11/2015
Nr Instances: 4
Nr Exposed: 1
Abatement Date: 08/28/2015
Gravity: 10
Report ID: 0418800
Contest Date:
Final Order: 09/01/2015
Related Event Code (REC):
Emphasis:
| Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
|---|---|---|---|---|---|---|
| Penalty | I: Informal Settlement | 09/01/2015 | $5,390.00 | 08/28/2015 | Serious | |
| Penalty | Z: Issued | 08/11/2015 | $5,390.00 | 08/28/2015 | Serious |
Text For Citation: 01 Item/Group: 002A Hazard:
29 CFR 1910.305(g)(1)(iv)(A): Flexible cords and/or cables were used as a substitute for the fixed wiring of a structure: (a) On or about April 3, 2015, at the above addressed worksite, the Fill-Rite pumps on two 1000 gallon diesel storage tanks were wired with temporary wiring and plugged into a wall receptacle, exposing the employees to the hazards of electrical shock/burns and/or fire and explosions. (b) On or about April 3, 2015, at the above addressed worksite, the NexGen Coriolis Flow Transmitter in the biodiesel storage area was wired with temporary wiring and plugged into a multiple outlet strip then further plugged into a wall receptacle, exposing employees to the hazards of electrical shock/burns and/or fire and explosions. (c) On or about April 3, 2015, at the above addressed worksite, the ChemTech PulsaFeeder pump on top of the BioExtend tote in the biodiesel storage area was wired with temporary wiring, run in series with another flow switch and then plugged into a wall receptacle, exposing employees to the hazards of electrical shock/burns and/or fire and explosions. (d) On or about April 3, 2015, at the above addressed worksite, the McDonnell & Miller Flow Switch located in the biodiesel storage area was wired with temporary wiring, run in series with the ChemTech PulsaFeeder and then plugged into a wall receptacle, exposing employees to the hazards of electrical shock/burns and/or fire and explosions.
Translate