Violation Detail
Standard Cited: 19100027 C01 Scaffolds and rope descent systems.
Inspection Nr: 1016368.015
Citation: 01002A
Citation Type: Other
Abatement Status: Abatement Completed
Initial Penalty: $3,600.00
Current Penalty: $3,600.00
Issuance Date: 03/25/2015
Nr Instances: 1
Nr Exposed: 32
Abatement Date: 05/11/2015
Gravity:
Report ID: 0524500
Contest Date: 05/08/2015
Final Order: 10/15/2015
Related Event Code (REC): R
Emphasis:
| Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
|---|---|---|---|---|---|---|
| Penalty | F: Formal Settlement | 10/15/2015 | $3,600.00 | 05/11/2015 | Other | |
| Penalty | C: Contested | 05/12/2015 | $3,600.00 | 05/11/2015 | Serious | |
| Penalty | Z: Issued | 03/25/2015 | $3,600.00 | 05/11/2015 | Serious |
Text For Citation: 01 Item/Group: 002A Hazard:
29 CFR 1910.27(c)(1): On fixed ladders, the perpendicular distance from the centerline of the rungs to the nearest permanent object on the climbing side of the ladder was not 36 inches for a pitch of 76 degrees, and 30 inches for a pitch of 90 degrees: Employees were exposed to a fall hazard at Unit 6 Grade Floor by the 62 Boiler because the distance from the centerline of the rungs to the 622 GR Fan Motor in front of the fixed ladder located next to the 621 Economizer Tank was 24 inches.