Violation Detail
Standard Cited: 19100119 J04 III Process safety management of highly hazardous chemicals.
Inspection Nr: 963743.015
Citation: 01002
Citation Type: Serious
Abatement Status: Abatement Completed
Initial Penalty: $7,000.00
Current Penalty: $7,000.00
Issuance Date: 09/03/2014
Nr Instances: 2
Nr Exposed: 33
Abatement Date: 12/01/2014
Gravity: 10
Report ID: 0626300
Contest Date:
Final Order: 09/24/2014
Related Event Code (REC):
Emphasis:
| Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
|---|---|---|---|---|---|---|
| Penalty | I: Informal Settlement | 09/24/2014 | $7,000.00 | 12/01/2014 | Serious | |
| Penalty | Z: Issued | 09/03/2014 | $7,000.00 | 09/22/2014 | Serious |
Text For Citation: 01 Item/Group: 002 Hazard:
29 CFR 1910.119(j)(4)(iii): The frequency of inspections and tests of process equipment was not consistent with applicable manufacturers' recommendations and good engineering practices, and more frequently if determined to be necessary by prior operating experience. The employer did not ensure the frequency of inspections and tests were followed. A. The violation occurred in the Gas Processing/NRU Facility on or about March 18, 2014 and times prior thereto where the employer failed to ensure the frequency of testing and inspections safety instrumented systems were conducted in accordance with the safety integrity level analysis and the employer's mechanical integrity program: a. Interlock/SIS 326 b. Interlock/SIS 329 c. Interlock/SIS 100 d. Interlock/SIS 111 e. Interlock/SIS 120 f. Interlock/SIS 180 g. Interlock/SIS 190 h. Interlock/SIS 193 i. Interlock/SIS 268
Translate