Violation Detail
Standard Cited: 19100106 E02 II B 2 Flammable liquids.
Inspection Nr: 959018.015
Citation: 01002
Citation Type: Serious
Abatement Status: Abatement Completed
Initial Penalty: $3,000.00
Current Penalty: $2,250.00
Issuance Date: 08/06/2014
Nr Instances: 1
Nr Exposed: 66
Abatement Date: 08/08/2014
Gravity: 1
Report ID: 0213100
Contest Date:
Final Order: 08/29/2014
Related Event Code (REC):
Emphasis:
| Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
|---|---|---|---|---|---|---|
| Penalty | I: Informal Settlement | 08/29/2014 | $2,250.00 | 08/08/2014 | Serious | |
| Penalty | Z: Issued | 08/06/2014 | $3,000.00 | 08/08/2014 | Serious |
Text For Citation: 01 Item/Group: 002 Hazard:
29 CFR 1910.106(e)(2)(ii)(b)(2): The quantity of Category 2, 3 or 4 flammable liquid located outside of an inside storage room or storage cabinet in a building or in any one fire area of a building exceeded 120 gallons: a) Chemical Storage Area - On and prior to February 10, 2014, the quantity of category 2 flammable liquids located outside of flammable storage cabinets was approximately 160 gallons in a room that did not meet the requirements of a flammable storage room. The chemicals in storage included, but were not limited to, Isopropyl Alcohol and Ethyl Alcohol.
Translate