Violation Detail
Standard Cited: 19100106 F03 III Flammable liquids.
Inspection Nr: 954981.015
Citation: 01002
Citation Type: Serious
Abatement Status: Abatement Completed
Initial Penalty: $2,000.00
Current Penalty: $1,700.00
Issuance Date: 07/08/2014
Nr Instances: 1
Nr Exposed: 6
Abatement Date: 07/25/2014
Gravity: 5
Report ID: 0213100
Contest Date:
Final Order: 07/24/2014
Related Event Code (REC):
Emphasis:
| Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
|---|---|---|---|---|---|---|
| Penalty | I: Informal Settlement | 07/24/2014 | $1,700.00 | 07/25/2014 | Serious | |
| Penalty | Z: Issued | 07/08/2014 | $2,000.00 | 07/25/2014 | Serious |
Text For Citation: 01 Item/Group: 002 Hazard:
29 CFR 1910.106(f)(3)(iii): Valves used for the final control for filling tank vehicles were not manually held open or equipped with automatic means for shutting off the flow when the vehicle is full or after filling of a preset amount: a) Loading Station closest to Harris Road, on or about 01/15/2014; The fuel arm, designed to be manually held open was tied open by a rope. The automatic shut off was not designed to engage at a preset amount or when full, but instead was set to shut off at 30 minutes.