Violation Detail
Standard Cited: 19100107 C06 Spray finishing using flammable and combustible materials.
Inspection Nr: 909304.015
Citation: 01002
Citation Type: Serious
Abatement Status: Abatement Completed
Initial Penalty: $2,100.00
Current Penalty: $1,050.00
Issuance Date: 07/23/2013
Nr Instances: 1
Nr Exposed: 2
Abatement Date: 08/06/2013
Gravity: 1
Report ID: 0111500
Contest Date:
Final Order: 08/16/2013
Related Event Code (REC):
Emphasis:
| Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
|---|---|---|---|---|---|---|
| Penalty | I: Informal Settlement | 08/16/2013 | $1,050.00 | 08/06/2013 | Serious | |
| Penalty | Z: Issued | 07/23/2013 | $2,100.00 | 08/06/2013 | Serious |
Text For Citation: 01 Item/Group: 002 Hazard:
29 CFR 1910.107(c)(6): Electrical wiring, motors, and other equipment outside of but within twenty (20) feet of any spray area, and not separated therefrom by partitions, produced sparks under normal operating conditions and did not otherwise conform to the provisions of subpart S of this part for Class I, Division 2 Hazardous Locations: Facility: An electrical outlet located outside of but within twenty (20) feet of a spraying area was not separated therefrom by partitions and did not otherwise conform to the provisions of subpart S of this part for Class I, Division 2 locations.