Violation Detail
Standard Cited: 19100106 E02 IV D Flammable liquids.
Inspection Nr: 908983.015
Citation: 01002
Citation Type: Serious
Abatement Date: 02/13/2014 2
Initial Penalty: $2,000.00
Current Penalty: $1,268.00
Issuance Date: 11/27/2013
Nr Instances: 1
Nr Exposed: 13
Related Event Code (REC):
Gravity: 5
Report ID: 0214200
Contest Date: 12/16/2013
Final Order: 04/24/2014
Emphasis:
Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
---|---|---|---|---|---|---|
Penalty | F: Formal Settlement | 04/24/2014 | $1,268.00 | 02/13/2014 | Serious | |
Penalty | C: Contested | 12/18/2013 | $2,000.00 | 01/16/2014 | Serious | |
Penalty | Z: Issued | 11/27/2013 | $2,000.00 | 01/16/2014 | Serious |
Text For Citation: 01 Item/Group: 002 Hazard:
29 CFR 1910.106(e)(2)(iv)(d): Flammable liquids were not drawn from or transferred into vessels, containers, or portable tanks within a building only through a closed piping system, from safety cans, by means of a device drawing through the top, or from a container or portable tanks by gravity through an approved self-closing valve: a) Establishment - cylinder charging room Employees dispensed acetone, a Category 1 flammable liquid, into compressed gas cylinders through in-plant piping with manually closing valves. Violation observed on or about 5/30/2013.