Violation Detail
Standard Cited: 19100119 F01 Process safety management of highly hazardous chemicals.
This violation item has been deleted.
Inspection Nr: 908161.015
Citation: 01002
Citation Type: Serious
Abatement Status: Abatement Completed
Initial Penalty: $7,000.00
Current Penalty: $0.00
Issuance Date: 11/21/2013
Nr Instances: 2
Nr Exposed: 18
Abatement Date: 12/11/2013
Gravity: 10
Report ID: 0626300
Contest Date: 12/10/2013
Final Order: 07/23/2014
Related Event Code (REC):
Emphasis:
Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
---|---|---|---|---|---|---|
Penalty | C: Contested | 03/16/2015 | $7,000.00 | 12/11/2013 | Serious | |
Penalty | F: Formal Settlement | 07/23/2014 | $0.00 | 12/11/2013 | Serious | |
Penalty | Z: Issued | 11/21/2013 | $7,000.00 | 12/11/2013 | Serious |
Text For Citation: 01 Item/Group: 002 Hazard:
29 CFR 1910.119(f)(1): The employer did not develop and implement written operating procedures that provide clear instructions for safely conducting activities involved in each covered process consistent with the process safety information: The employer does not ensure that written operating procedures are developed and implemented to provide clear instructions for changing temperature alarm setpoints for high temperature separator (HTS), 30-V-1. This violation occurred on or about August 5, 2013, and at times prior thereto, in the Naphtha Hydrotreater (unit 30); where employees were exposed to inhalation, fire, and explosion hazards from potential releases of hazardous materials without developed and implemented written operating procedures to provide clear instructions for changing temperature alarm setpoints for following instances. a. High high and process high alarm temperature setpoints were changed from 500F to 440F and from 500F to 430F respectively. These temperature alarm setpoints are associated with a temperature indicator (30-TI021) which indicates temperature of the stream from a heat exchanger (30-E-1C) to HTS (30-V-1). b. High high and process high alarm temperature setpoints were changed from 600F to 440F and from 500F to 430F respectively. These temperature alarm setpoints are associated with a temperature indicator (30-TI035) which indicates temperature of the stream from a heat exchanger (30-E-1A) to HTS (30-V-1).