Violation Detail
Standard Cited: 19100119 F01 I C Process safety management of highly hazardous chemicals.
Inspection Nr: 906171.015
Citation: 01002
Citation Type: Other
Abatement Status: Abatement Completed
Initial Penalty: $5,000.00
Current Penalty: $0.00
Issuance Date: 10/08/2013
Nr Instances: 9
Nr Exposed: 100
Abatement Date: 11/26/2013
Gravity:
Report ID: 0523400
Contest Date:
Final Order: 10/28/2013
Related Event Code (REC): R
Emphasis:
| Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
|---|---|---|---|---|---|---|
| Penalty | I: Informal Settlement | 10/28/2013 | $0.00 | 11/26/2013 | Other | |
| Penalty | Z: Issued | 10/08/2013 | $5,000.00 | 11/26/2013 | Serious |
Text For Citation: 01 Item/Group: 002 Hazard:
29 CFR 1910.119(f)(1)(i)(C): The employer did not develop and implement written operating procedures that provide clear instructions for safely conducting temporary operations. Written operating procedures did not contain specifications for transition from normal operations to temporary/emergency operations for the following procedures (but not limited to): (a) High Stage TS Cooled Screw Compressors: The procedure did not specify actions to be taken by the operator(s) when the Operating Limit Discharge Pressure, Suction Pressure and Discharge Temperature exceed normal operating range. (b) High Stage LI Cooled Screw Compressors: The procedure did not specify actions to be taken by the operator(s) when the Operating Limit Discharge Pressure, Suction Pressure, Discharge Temperature and lubrication oil temperature exceed normal operating range. (c) High Stage Reciprocating Compressors: The procedure did not specify actions to be taken by the operator(s) when the Operating Limit Discharge Pressure, Suction Pressure, Discharge Temperature and Lubrication Oil Temperature exceed normal operating range. (d) Evaporative Condensers: The procedure did not specify actions to be taken by the operator(s) when the Evaporative Condensers condensing pressure Operating Limit exceed normal operating range. (e) Thermosyphon Receiver: The procedure did not specify actions to be taken by the operator(s) when the Operating Limit Pressure and Operating Limit Level exceed normal operating range. (f) High Pressure Receiver: The procedure did not specify actions to be taken by the operator(s) when the Operating Limit Pressure and Operating Limit level exceed normal operating range. (g) High Temp Accumulator/Intercooler: The procedure did not specify actions to be taken by the operator(s) when the Operating Limit Pressure and Operating Level exceed normal operating range. (h) Low Temperature Recirculator: The procedure did not specify actions to be taken by the operator(s) when the Operating Limit Pressure and Operating Limit Level exceed normal operating range. (i) Flooded S&T Water Chiller with Oil Pot: The procedure did not specify actions to be taken by the operator(s) when the Operating Limit Pressure and Surge Drum Level Operating Limit exceed normal operating range.
Translate