Powered by GoogleTranslate

Violation Detail

Standard Cited: 19100332 B01 Training

Inspection Nr: 447613.015

Citation: 01002

Citation Type: Serious

Abatement Status: Abatement Completed

Initial Penalty: $5,000.00

Current Penalty: $3,750.00

Issuance Date: 09/06/2012

Nr Instances: 2

Nr Exposed: 4

Abatement Date: 10/19/2012

Gravity: 5

Report ID: 0213600

Contest Date:

Final Order: 09/14/2012

Related Event Code (REC): C

Emphasis:


Penalty and Failure to Abate Event History
Type Latest Event Event Date Penalty Abatement Due Date Citation Type Failure to Abate Inspection
Penalty I: Informal Settlement 09/14/2012 $3,750.00 10/19/2012 Serious  
Penalty Z: Issued 09/06/2012 $5,000.00 10/19/2012 Serious  

Text For Citation: 01 Item/Group: 002 Hazard:

29 CFR 1910.332(b)(1): Employees were not trained in and familiar with the safety-related work practices required by 1910.331 through 1910.335 that pertained to their respective job assignments: a) On or about 4/1/12 thru 6/7/12 in various areas of St. John Fisher College, Rochester, NY: Electricians and HVAC Technicians perform installation, maintenance, & repair of electrical equipment, including voltage testing & troubleshooting live on circuits up to 480 volts-ac where they are potentially exposed to shock and arc flash hazards which necessated the use of Personal Protective Equipment (PPE) for eyes, face, head, torso,hands, and extremities. These employees were not trained and familiar with requirements to wear appropriate PPE for the tasks they performed, and how to select the proper PPE for the task. b) On or about 4/1/12 thru 6/7/12 in various areas of St. John Fisher College, Rochester, NY: Electricians and HVAC Technicians perform installation, maintenance, & repair of electrical equipment, including voltage testing & troubleshooting live on circuits up to 480 volts-ac and work on de-energized circuits. These employees were not trained and familiar with the requirement to de-energize and lockout before performing electrical work and under what circumstances it is permissible to work on/near energized parts. ABATEMENT CERTIFICATION REQUIRED

Thank You for Visiting Our Website

You are exiting the Department of Labor's Web server.

The Department of Labor does not endorse, takes no responsibility for, and exercises no control over the linked organization or its views, or contents, nor does it vouch for the accuracy or accessibility of the information contained on the destination server. The Department of Labor also cannot authorize the use of copyrighted materials contained in linked Web sites. Users must request such authorization from the sponsor of the linked Web site. Thank you for visiting our site. Please click the button below to continue.

Close