Violation Detail
Standard Cited: 19100111 B09 IX Storage and handling of anhydrous ammonia.
This violation item has been deleted.
Inspection Nr: 315973859
Citation: 01002
Citation Type: Serious
Abatement Status:
Initial Penalty: $7,000.00
Current Penalty: $7,000.00
Issuance Date: 06/06/2012
Nr Instances: 1
Nr Exposed: 11
Abatement Date: 06/25/2012
Gravity: 10
Report ID: 0627100
Contest Date:
Final Order:
Related Event Code (REC):
Emphasis:
| Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
|---|---|---|---|---|---|---|
| Penalty | I: Informal Settlement | 06/29/2012 | $7,000.00 | 06/25/2012 | Serious | |
| Penalty | Z: Issued | 06/06/2012 | $7,000.00 | 06/25/2012 | Serious |
Text For Citation: 01 Item/Group: 002 Hazard: CHEMNEP
29 CFR 1910(b)(9)(ix): A hydrostatic relief valve was not installed between each pair of valves in the liquid ammonia piping or hose where liquid could be trapped so as to relieve into the atmosphere at a safe location: The employer does not ensure that a relief valve is provided between each pair of block valves in the liquid ammonia piping where liquid could become trapped. Relief for a portion of line 2376 was not provided should liquid be trapped the employer must submit documentation showing that it is in compliance with the standard, including describing the steps that it is taking to ensure that specific safety systems and their functions are listed in its operating procedures.