Violation Detail
Standard Cited: 19100132 F01 General requirements.
Inspection Nr: 315156612
Citation: 01002
Citation Type: Serious
Abatement Status: X
Initial Penalty: $4,000.00
Current Penalty: $2,000.00
Issuance Date: 06/03/2011
Nr Instances: 1
Nr Exposed: 5
Abatement Date: 07/20/2011
Gravity: 05
Report ID: 0521700
Contest Date:
Final Order:
Related Event Code (REC): R
Emphasis:
| Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
|---|---|---|---|---|---|---|
| Penalty | I: Informal Settlement | 06/28/2011 | $2,000.00 | 07/20/2011 | Serious | |
| Penalty | Z: Issued | 06/03/2011 | $4,000.00 | 07/20/2011 | Serious |
Text For Citation: 01 Item/Group: 002 Hazard: UNCLASS
furnish employment and a place of employment which were free from recognized hazards that were causing or likely to cause death or serious physical harm to employees in that employees were potentially exposed to an oxygen-deficient atmosphere associated with nitrogen: On or about May 5, 2011, in the facility, employees were not adequately protected against the release of nitrogen and an oxygen deficient atmosphere in that: a. The process room where employees operated equipment (hamburger making machine, spiral freezer) that used nitrogen was not provided with a gas detection and alarm system to warn employees of a release of nitrogen in excess of the allowable limit (lowering the oxygen level below 19.5%). Among other feasible and acceptable methods to control these hazards would be to comply with the guidelines outlined in the Compressed Gas Association, Inc. Safety