Powered by GoogleTranslate

Violation Detail

Standard Cited: 19100119 D03 IB Process safety management of highly hazardous chemicals.

This violation item has been deleted.

Inspection Nr: 313130833

Citation: 01002

Citation Type: Serious

Abatement Status: X

Initial Penalty: $2,250.00

Current Penalty:

Issuance Date: 04/16/2010

Nr Instances: 5

Nr Exposed: 12

Abatement Date: 04/29/2010

Gravity: 03

Report ID: 0523300

Contest Date: 05/07/2010

Final Order: 09/06/2011

Related Event Code (REC): R

Emphasis:


Penalty and Failure to Abate Event History
Type Latest Event Event Date Penalty Abatement Due Date Citation Type Failure to Abate Inspection
Penalty F: Formal Settlement 09/06/2011 04/29/2010 Serious  
Penalty Z: Issued 04/16/2010 $2,250.00 04/29/2010 Serious  

Text For Citation: 01 Item/Group: 002 Hazard: CHEMNEP

29 CFR 1910.119(d)(3)(i)(B): Process safety information pertaining to the equipment in the process did not include the piping and instrument diagrams (P&ID'S): The employer did not ensure that the process safety information depicted on the P&IDs was accurate and up-to-date. a) The P&ID provided indicated the presence of two flame arresters, one on the dirty solvent tank, one on the clean solvent tank, which were not present. b) The P&ID provided did not indicate the piping associated with the incoming Ethyl Acetate from the bulk off loading area, and subsequently connecting to the Ink Room. c) The P&ID provided did not include the LEL detector located in the ventilation duct work to the oxidizer that interlocks the controls for operation of the Renzmann Wash Units.nn

Thank You for Visiting Our Website

You are exiting the Department of Labor's Web server.

The Department of Labor does not endorse, takes no responsibility for, and exercises no control over the linked organization or its views, or contents, nor does it vouch for the accuracy or accessibility of the information contained on the destination server. The Department of Labor also cannot authorize the use of copyrighted materials contained in linked Web sites. Users must request such authorization from the sponsor of the linked Web site. Thank you for visiting our site. Please click the button below to continue.