Violation Detail
Standard Cited: 19100119 D02 ID Process safety management of highly hazardous chemicals.
Inspection Nr: 311611081
Citation: 01002
Citation Type: Serious
Abatement Date: 04/05/2010 X
Initial Penalty: $5,000.00
Current Penalty: $5,000.00
Issuance Date: 03/08/2010
Nr Instances: 2
Nr Exposed: 25
Related Event Code (REC):
Gravity: 10
Report ID: 0524700
Contest Date: 03/31/2010
Final Order: 09/27/2018
Emphasis:
Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
---|---|---|---|---|---|---|
Penalty | R: Review Commission | 09/27/2018 | $5,000.00 | 01/24/2019 | Serious | |
Penalty | Z: Issued | 03/08/2010 | $5,000.00 | Serious |
Text For Citation: 01 Item/Group: 002 Hazard: REFINERY
29 CFR 1910.119(d)(2)(i)(D): Process safety information pertaining to the techno logy of the process did not include the safe upper and lower limits for such ite ms as temperatures, pressures, flows or compositions: a.BP-Husky Refining, LLC - Oregon, Ohio: On or about September 10, 2009, the employer did not ensure heat transfer information for the refractory lined FCC Reactor (PR 511024), located i n the FCC unit, were calculated to determine the vessel wall temperatures in com parison with the design metal temperatures when operating at the maximum interna l temperature of 1050 degrees F. b.BP-Husky Refining, LLC - Oregon, Ohio: On or about September 10, 2009, the employer did not ensure heat transfer calculations for the refractory lined FCC Regenerator (PR 511023), located in the FCC unit, were calculated to determine the vessel wall temperatures in comparison with the design metal temperatures wh en operating at the maximum internal temperature 1400 degrees F. In accordance w ith 29 CFR 1903.19(d), abatement certification is required for this violation (u sing the CERTIFICATION OF CORRECTIVE ACTION WORKSHEET), and in addition, documen tation demonstrating that abatement is complete must be included with your certi fication. This documentation may include, but is not limited to, evidence of the purchase or repair of the equipment, photographic or video evidence of abatemen t, or other written records.