Violation Detail
Standard Cited: 19100119 D03 I Process safety management of highly hazardous chemicals.
Inspection Nr: 311592661
Citation: 01002
Citation Type: Serious
Abatement Status: X
Initial Penalty: $7,000.00
Current Penalty: $5,250.00
Issuance Date: 05/27/2010
Nr Instances: 4
Nr Exposed: 150
Abatement Date: 08/31/2010
Gravity: 10
Report ID: 0111700
Contest Date:
Final Order:
Related Event Code (REC):
Emphasis:
| Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
|---|---|---|---|---|---|---|
| Penalty | I: Informal Settlement | 06/21/2010 | $5,250.00 | 08/31/2010 | Serious | |
| Penalty | Z: Issued | 05/27/2010 | $7,000.00 | 06/29/2010 | Serious |
Text For Citation: 01 Item/Group: 002 Hazard: CHEMNEP
29 CFR 1910.119(d)(3)(i): Process safety information pertaining to the equipment in the process did not include the elements specified in 29 CFR 1910.119(d)(3)(i)(A) through (H): a.Site - Process safety information for the ammonia refrigeration system did not include information related to pipe specifications and minimum acceptable thicknesses. b.Site - Process safety information for the ammonia refrigeration system did not include information described within the ASME U1A report related to pressure vessels. Such information included, but was not limited to, nominal thicknesses and corrosion allowances for the shell and heads of the vessels as well as the maximum allowable working pressure. c.Site - Process safety information for the ammonia refrigeration system did not include information related to vibration in ammonia compressors and cryolators. d.Site - Process safety information for the ammonia refrigeration system did not include information related to gauges and thermometers used in the system.
Translate