Violation Detail
Standard Cited: 19100119 E06 Process safety management of highly hazardous chemicals.
Inspection Nr: 1843132.015
Citation: 01002
Citation Type: Serious
Abatement Status:
Initial Penalty: $16,550.00
Current Penalty: $16,550.00
Issuance Date: 02/09/2026
Nr Instances: 1
Nr Exposed: 14
Abatement Date: 03/27/2026
Gravity: 10
Report ID: 0317500
Contest Date: 02/27/2026
Final Order:
Related Event Code (REC): A
Emphasis:
| Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
|---|---|---|---|---|---|---|
| Penalty | C: Contested | 02/27/2026 | $16,550.00 | 03/27/2026 | Serious | |
| Penalty | Z: Issued | 02/09/2026 | $16,550.00 | 03/27/2026 | Serious |
Text For Citation: 01 Item/Group: 002 Hazard:
29 CFR 1910.119(e)(6): The employer did not update and revalidate by a team meeting the requirements in paragraph (e)(4) of this section, to assure that the process hazard analysis is consistent with the current process, at least every five (5) years after the completion of the initial process hazard analysis: a) At the Clairton Plant, on or about August 11, 2025 - The employer did not update and revalidate the 1998 Underfire Gas System Operability and PHA Report at least every five years. The most recent updated and revalidated process hazard analysis of the Underfire Gas System was conducted in November of 2018. Failure to update and revalidate the initial PHA of the Underfire Gas System at least every five years exposed employees working in and around the process to an explosion hazard when cryogenically-processed coke oven gas was released from 13 Pad Valve.