Violation Detail
Standard Cited: 19100304 B03 I Wiring design and protection.
Inspection Nr: 1805402.015
Citation: 01002
Citation Type: Serious
Abatement Status: Abatement Completed
Initial Penalty: $6,383.00
Current Penalty: $4,148.95
Issuance Date: 07/08/2025
Nr Instances: 1
Nr Exposed: 18
Abatement Date: 07/22/2025
Gravity: 5
Report ID: 0215300
Contest Date:
Final Order: 07/14/2025
Related Event Code (REC):
Emphasis:
| Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
|---|---|---|---|---|---|---|
| Penalty | I: Informal Settlement | 07/14/2025 | $4,148.95 | 07/22/2025 | Serious | |
| Penalty | Z: Issued | 07/08/2025 | $6,383.00 | 07/22/2025 | Serious |
Text For Citation: 01 Item/Group: 002 Hazard:
29 CFR 1910.304(b)(3)(i): All 125-volt, single-phase, 15- and 20-ampere receptacles installed in wet locations were not equipped with ground-fault circuit-interrupter protection for personnel. a) On or about February 20, 2025, at the Elysian Beach Resort, near kitchen sink in the Break Room, the employer did not ensure that an electrical receptacle was equipped with ground-fault circuit-interrupter (GFCI) protection, exposing employees to electrical hazards. NOTE: Certification and documentation of abatement must be submitted for this citation item as required by CFR 1903.19(c) and (d), respectively.