Violation Detail
Standard Cited: 19100106 B06 Flammable liquids.
Inspection Nr: 1793673.015
Citation: 01002
Citation Type: Serious
Abatement Status: Corrected During Inspection
Initial Penalty: $14,895.00
Current Penalty: $9,500.00
Issuance Date: 05/27/2025
Nr Instances: 1
Nr Exposed: 4
Abatement Date:
Gravity: 10
Report ID: 0521400
Contest Date:
Final Order: 06/17/2025
Related Event Code (REC): A
Emphasis:
Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
---|---|---|---|---|---|---|
Penalty | I: Informal Settlement | 06/17/2025 | $9,500.00 | Serious | ||
Penalty | Z: Issued | 05/27/2025 | $14,895.00 | Serious |
Text For Citation: 01 Item/Group: 002 Hazard:
29 CFR 1910.106(b)(6): "Sources of ignition." In locations where flammable vapors may be present, precautions shall be taken to prevent ignition by eliminating or controlling sources of ignition. Sources of ignition may include open flames, lightning, smoking, cutting and welding, hot surfaces, frictional heat, sparks (static, electrical, and mechanical), spontaneous ignition, chemical and physical-chemical reactions, and radiant heat. On or about December 16, 2024, employees were exposed to flammable vapors in the 'Tinter's Row' Room of the North Building. The presence of these vapors was attributed (but not limited) to the purging of aerosol cans. The employer did not ensure sufficient safeguards were in place to prevent sparks generated by the frictional heat of steel aerosol cans from making contact with the surrounding environment, including (but not limited to) steel Intermediate Bulk Container (IBC) totes as well as the concrete floor.