Violation Detail
Standard Cited: 19100305 B01 II Wiring methods, components, and equipment for general use.
Inspection Nr: 1782336.015
Citation: 01002
Citation Type: Serious
Abatement Status: Corrected During Inspection
Initial Penalty: $4,884.00
Current Penalty: $3,418.80
Issuance Date: 02/03/2025
Nr Instances: 1
Nr Exposed: 5
Abatement Date:
Gravity: 1
Report ID: 0728900
Contest Date:
Final Order: 03/03/2025
Related Event Code (REC):
Emphasis:
| Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
|---|---|---|---|---|---|---|
| Penalty | I: Informal Settlement | 03/03/2025 | $3,418.80 | Serious | ||
| Penalty | Z: Issued | 02/03/2025 | $4,884.00 | Serious |
Text For Citation: 01 Item/Group: 002 Hazard:
29 CFR 1910.305(b)(1)(ii): Unused openings in boxes, cabinets, or fittings were not effectively closed: On or about October 16, 2024, employees engaged in grain operations at 16515 County Road 14, Chappell, Nebraska 69129, were exposed to fire and explosion hazards in that the employer did not ensure that all unused openings in electrical conduit fittings were closed to prevent becoming an ignition source to the combustible grain dust produced under normal operations.