Violation Detail
Standard Cited: 19100305 G01 IV B Wiring methods, components, and equipment for general use.
Inspection Nr: 1762762.015
Citation: 01002
Citation Type: Serious
Abatement Status: Abatement Completed
Initial Penalty: $8,067.00
Current Penalty: $4,437.00
Issuance Date: 08/29/2024
Nr Instances: 3
Nr Exposed: 10
Abatement Date: 09/11/2024
Gravity: 5
Report ID: 0936400
Contest Date:
Final Order: 09/27/2024
Related Event Code (REC):
Emphasis:
| Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
|---|---|---|---|---|---|---|
| Penalty | I: Informal Settlement | 09/27/2024 | $4,437.00 | 09/11/2024 | Serious | |
| Penalty | Z: Issued | 08/29/2024 | $8,067.00 | 09/11/2024 | Serious |
Text For Citation: 01 Item/Group: 002 Hazard:
29 CFR 1910.305(g)(1)(iv)(B):Unless specifically permitted otherwise in paragraph (g)(1)(ii) of this section, flexible cords and cables may not be used where run through holes in walls, ceilings, or floors. A.) KITCHEN: On or about 07-17-2024 and times prior too, a flexible cord was run through the ceiling tiles and over a wall to power an reverse osmosis system exposing employees to fire dangers. B.) LAUNDRY: On or about 07-17-2024 and times prior too, a flexible cord was run through the wall to power laundry equipment exposing employees to fire dangers. C.) LOBBY EXIT: On or about 07-17-2024 and times prior too, a flexible cord was run through the aluminum door frame exposing employees to fire dangers.