Violation Detail
Standard Cited: 19100106 E02 II B 2 Flammable liquids.
Inspection Nr: 1749202.015
Citation: 01002
Citation Type: Serious
Abatement Status: Abatement Completed
Initial Penalty: $8,067.00
Current Penalty: $4,033.50
Issuance Date: 09/05/2024
Nr Instances: 1
Nr Exposed: 1
Abatement Date: 12/02/2024
Gravity: 5
Report ID: 0521100
Contest Date:
Final Order: 09/30/2024
Related Event Code (REC):
Emphasis:
Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
---|---|---|---|---|---|---|
Penalty | I: Informal Settlement | 09/30/2024 | $4,033.50 | 12/02/2024 | Serious | |
Penalty | Z: Issued | 09/05/2024 | $8,067.00 | 10/15/2024 | Serious |
Text For Citation: 01 Item/Group: 002 Hazard:
29 CFR 1910.106(e)(2)(ii)(b)(2): The quantity of liquid that may be located outside of an inside storage room or storage cabinet in a building or in any one fire area of a building shall not exceed 120 gallons of Category 2, 3, or 4 flammable liquids in containers: On or about May 21, 2024, at a facility located at 811 S. Neenah Avenue in Sturgeon Bay, WI; the employer had greater than 120 gallons of Category 2, 3, or 4 flammable liquids in the Paint area located outside of an inside storage room or storage cabinets. Approximately 470 gallons of flammable liquids in containers, consisting of approximately five (5) 55-gallon drums and at least 39 5-gallon buckets, were located in the room where the paint booths were located.