Violation Detail
Standard Cited: 19100106 E02 II B 2 Flammable liquids.
Inspection Nr: 1744358.015
Citation: 01002
Citation Type: Serious
Abatement Status: Abatement Completed
Initial Penalty: $11,292.00
Current Penalty: $6,775.20
Issuance Date: 07/01/2024
Nr Instances: 1
Nr Exposed: 4
Abatement Date: 08/05/2024
Gravity: 10
Report ID: 0728900
Contest Date:
Final Order: 07/17/2024
Related Event Code (REC):
Emphasis:
Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
---|---|---|---|---|---|---|
Penalty | I: Informal Settlement | 07/17/2024 | $6,775.20 | 08/05/2024 | Serious | |
Penalty | Z: Issued | 07/01/2024 | $11,292.00 | 08/05/2024 | Serious |
Text For Citation: 01 Item/Group: 002 Hazard:
29 CFR 1910.106(e)(2)(ii)(b)(2):The quantity of Category 2, 3 or 4 flammable liquid located outside of an inside storage room or storage cabinet in a building or in any one fire area of a building exceeded 120 gallons: The employer is exposing employees to fire and explosion hazards. This was most recently documented on April 24, 2024, at 84504 North State Highway 11, Burwell, Nebraska. Below the storage rack in the paint shed, the following but not limited to flammable liquids were observed being stored outside of a flammable storage area. (a) - 4 barrels of 'Rowse Red Red' paint with 189.25 Liters or approximately 50 gallons inside totaling about 200 gallons (b) - 15 containers of 'Urethane Hardener' with 18.95 Liters or approximately 5 gallons inside totaling about 75 gallons