Violation Detail
Standard Cited: 19100333 B02 IV Selection and use of work practices
Inspection Nr: 1740812.015
Citation: 01002
Citation Type: Serious
Abatement Status: Abatement Completed
Initial Penalty: $16,131.00
Current Penalty: $11,000.00
Issuance Date: 08/21/2024
Nr Instances: 1
Nr Exposed: 2
Abatement Date: 09/19/2024
Gravity: 10
Report ID: 0521100
Contest Date:
Final Order: 09/23/2024
Related Event Code (REC):
Emphasis:
| Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
|---|---|---|---|---|---|---|
| Penalty | I: Informal Settlement | 09/23/2024 | $11,000.00 | 09/19/2024 | Serious | |
| Penalty | Z: Issued | 08/21/2024 | $16,131.00 | 09/19/2024 | Serious |
Text For Citation: 01 Item/Group: 002 Hazard:
29 CFR 1910.333(b)(2)(iv): Verification of deenergized condition. The requirements of this paragraph shall be met before any circuits or equipment can be considered and worked as deenergized. On or about April 1, 2024, at a jobsite located at 1919 South Broadway Street, in Green Bay, Wisconsin; in Building 141 on the second floor MCC Room, verification of de-energization of the 4160V switchgear on the load side and line side was not conducted prior to pulling wires for the Boiler 10 project exposing employees to electrical shock hazards.