Powered by GoogleTranslate

Violation Detail

Standard Cited: 19100253 B04 III Oxygen-fuel gas welding and cutting.

Inspection Nr: 1729908.015

Citation: 01002

Citation Type: Serious

Abatement Status: Abatement Completed

Initial Penalty: $0.00

Current Penalty: $0.00

Issuance Date: 08/19/2024

Nr Instances: 1

Nr Exposed: 28

Abatement Date: 09/13/2024

Gravity: 5

Report ID: 0134000

Contest Date: 09/10/2024

Final Order: 09/18/2024

Related Event Code (REC):

Emphasis:


Penalty and Failure to Abate Event History
Type Latest Event Event Date Penalty Abatement Due Date Citation Type Failure to Abate Inspection
Penalty F: Formal Settlement 09/18/2024 $0.00 09/13/2024 Serious  
Penalty C: Contested 09/11/2024 $0.00 09/13/2024 Serious  
Penalty Z: Issued 08/19/2024 $0.00 09/13/2024 Serious  

Text For Citation: 01 Item/Group: 002 Hazard:

29 CFR 1910.253(b)(4)(iii) - Oxygen cylinders in storage were not separated from fuel-gas cylinders or combustible materials (especially oil or grease), a minimum distance of 20 feet (6.1 m) or by a noncombustible barrier at least 5 feet (1.5 m) high having a fire-resistance rating of at least one-half hour: Location - HVAC service area, Building No. 61 On or about 02/20/24, an oxygen cylinder was stored in close proximity to an acetylene (fuel gas) cylinder.

Thank You for Visiting Our Website

You are exiting the Department of Labor's Web server.

The Department of Labor does not endorse, takes no responsibility for, and exercises no control over the linked organization or its views, or contents, nor does it vouch for the accuracy or accessibility of the information contained on the destination server. The Department of Labor also cannot authorize the use of copyrighted materials contained in linked Web sites. Users must request such authorization from the sponsor of the linked Web site. Thank you for visiting our site. Please click the button below to continue.