Violation Detail
Standard Cited: 19100119 D03 II Process safety management of highly hazardous chemicals.
Inspection Nr: 1691967.015
Citation: 01002
Citation Type: Other
Abatement Status: Abatement Completed
Initial Penalty: $16,131.00
Current Penalty: $8,000.00
Issuance Date: 02/07/2024
Nr Instances: 1
Nr Exposed: 3
Abatement Date: 04/16/2024
Gravity: 10
Report ID: 0627700
Contest Date:
Final Order: 03/07/2024
Related Event Code (REC):
Emphasis:
Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
---|---|---|---|---|---|---|
Penalty | I: Informal Settlement | 03/07/2024 | $8,000.00 | 04/16/2024 | Other | |
Penalty | Z: Issued | 02/07/2024 | $16,131.00 | 04/16/2024 | Serious |
Text For Citation: 01 Item/Group: 002 Hazard:
29 CFR 1910.119(d)(3)(ii): The employer did not document that equipment complies with recognized and generally accepted good engineering practices (RAGAGEP). On or about August 18, 2023, and at times prior thereto, the employer did not document that the machinery room complied with the employer's chosen RAGAGEP, IIAR 2 (2014) Standard for Safe Design of Closed Circuit Ammonia Refrigeration Systems, Sections 6.2.1 and 6.2.5 when the machinery room allowed for the passage of air to an area that employees routinely occupy. This exposed employees to anhydrous ammonia release hazards.