Violation Detail
Standard Cited: 19100303 F02 General.
This violation item has been deleted.
Inspection Nr: 1614212.015
Citation: 01002
Citation Type: Serious
Abatement Status: Corrected During Inspection
Initial Penalty: $10,360.00
Current Penalty: $0.00
Issuance Date: 10/19/2022
Nr Instances: 1
Nr Exposed: 20
Abatement Date:
Gravity: 5
Report ID: 0626300
Contest Date:
Final Order: 11/08/2022
Related Event Code (REC):
Emphasis:
| Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
|---|---|---|---|---|---|---|
| Penalty | I: Informal Settlement | 11/08/2022 | $0.00 | Serious | ||
| Penalty | Z: Issued | 10/19/2022 | $10,360.00 | Serious |
Text For Citation: 01 Item/Group: 002 Hazard:
29 CFR 1910.303(f)(2): Each service, feeder, and branch circuit, at its disconnecting means or overcurrent device, was not legibly marked to indicate its purpose, unless located and arranged so the purpose is evident: (a) On or about August 10, 2022, breaker box LC1 was found with its circuit breakers generally marked to indicate multiple workstations and dock packages but the purpose was not evident in that workstations and dock package(s) were not identified by numbers or other indicators exposing employees evaluating/troubleshooting dock door systems and their related components to an electrical shock hazard.