Violation Detail
Standard Cited: 19100119 D03 II Process safety management of highly hazardous chemicals.
Inspection Nr: 1592913.015
Citation: 01002
Citation Type: Serious
Abatement Status: Abatement Completed
Initial Penalty: $14,502.00
Current Penalty: $14,502.00
Issuance Date: 10/21/2022
Nr Instances: 3
Nr Exposed: 8
Abatement Date: 12/09/2022
Gravity: 10
Report ID: 0418100
Contest Date: 11/18/2022
Final Order: 10/06/2023
Related Event Code (REC): R
Emphasis:
Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
---|---|---|---|---|---|---|
Penalty | F: Formal Settlement | 10/06/2023 | $14,502.00 | 12/09/2022 | Serious | |
Penalty | C: Contested | 11/28/2022 | $14,502.00 | 12/09/2022 | Serious | |
Penalty | Z: Issued | 10/21/2022 | $14,502.00 | 12/09/2022 | Serious |
Text For Citation: 01 Item/Group: 002 Hazard:
29 CFR 1910.119(d)(3)(ii):The employer did not document that equipment complies with recognized and generally accepted good engineering practices. a) Plant; on or about April 25, 2022, the employer failed to determine and document compliance with recognized and generally accepted good engineering practices to protect employees exposed to anhydrous ammonia hazards as specified in ANSI/IIAR 2-1999 Equipment, Design, and Installation of Ammonia Mechanical Refrigeration Systems, section 7.5 Field Leak Testing Requirements, for the testing of the 16 in. diameter suction pipeline after weld repair.