Violation Detail
Standard Cited: 19100106 E06 II Flammable liquids.
Inspection Nr: 1586606.015
Citation: 01002
Citation Type: Serious
Abatement Status: Quick Fix
Initial Penalty: $4,754.00
Current Penalty: $3,000.00
Issuance Date: 05/19/2022
Nr Instances: 1
Nr Exposed: 3
Abatement Date:
Gravity: 1
Report ID: 0213600
Contest Date:
Final Order: 06/09/2022
Related Event Code (REC):
Emphasis:
Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
---|---|---|---|---|---|---|
Penalty | I: Informal Settlement | 06/09/2022 | $3,000.00 | Serious | ||
Penalty | Z: Issued | 05/19/2022 | $4,754.00 | Serious |
Text For Citation: 01 Item/Group: 002 Hazard:
29 CFR 1910.106(e)(6)(ii): Category 1 or 2 flammable liquids, or Category 3 flammable liquids with a flashpoint below 100 �F (37.8 �C), were dispensed into containers without the nozzle and container being electrically interconnected and grounded. a) On or about 03/30/2022; in the Painting Area, when employees pour flammable liquids such as but not limited to paint, paint thinner or acetone in a waste drum metal container without both containers being effectively bonded and grounded to prevent discharge sparks of static electricity, employees are exposed to fire hazards. NO ABATEMENT CERTIFICATION REQUIRED