Violation Detail
Standard Cited: 19100107 M01 Spray finishing using flammable and combustible materials.
This violation item has been deleted.
Inspection Nr: 1558512.015
Citation: 01002
Citation Type: Serious
Abatement Status:
Initial Penalty: $9,324.00
Current Penalty: $0.00
Issuance Date: 04/08/2022
Nr Instances: 1
Nr Exposed: 2
Abatement Date: 05/25/2022
Gravity: 5
Report ID: 0112000
Contest Date:
Final Order: 05/06/2022
Related Event Code (REC):
Emphasis:
Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
---|---|---|---|---|---|---|
Penalty | I: Informal Settlement | 05/06/2022 | $0.00 | 05/25/2022 | Serious | |
Penalty | Z: Issued | 04/08/2022 | $9,324.00 | 05/25/2022 | Serious |
Text For Citation: 01 Item/Group: 002 Hazard:
29 CFR 1910.107(m)(1):Spraying operations involving the use of organic peroxides and other dual component coatings were not conducted in approved sprinklered spray booths meeting the requirements of this section: Building 593 Spray Booths: On or about October 18, 2021, space within the interior of Spray Booth 5 and Spray Booth 6, on the downstream and upstream sides of the filters, was not protected with approved automatic sprinklers for spraying operations involving the use of dual component coatings including, but not limited to, S1193 Silicone Epoxy (Product Code: S-1193) and S1195 Thinner (Product Code: S1195).