Violation Detail
Standard Cited: 19260405 A02 II C Wiring methods, components, and equipment for general use.
Inspection Nr: 1548188.015
Citation: 01002
Citation Type: Serious
Abatement Status: Corrected During Inspection
Initial Penalty: $10,256.00
Current Penalty: $6,483.00
Issuance Date: 01/25/2022
Nr Instances: 1
Nr Exposed: 2
Abatement Date:
Gravity: 5
Report ID: 0215000
Contest Date: 02/18/2022
Final Order: 08/08/2022
Related Event Code (REC):
Emphasis:
Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
---|---|---|---|---|---|---|
Penalty | F: Formal Settlement | 08/08/2022 | $6,483.00 | Serious | ||
Penalty | C: Contested | 02/18/2022 | $10,256.00 | Serious | ||
Penalty | Z: Issued | 01/25/2022 | $10,256.00 | Serious |
Text For Citation: 01 Item/Group: 002 Hazard:
29 CFR 1926.405(a)(2)(ii)(C):Receptacles were connected to the same ungrounded conductor of multi-wire circuits supplying temporary lighting. Location: 3415 Farragut Road, Brooklyn, NY; 6th & 7th floor stairway landings. On or about 7/28/2021 a) Receptacles for uses other than temporary lighting were connected to the same ungrounded conductors of multi-wire circuits which supply temporary lighting. Receptacles not connected to ground.