Violation Detail
Standard Cited: 19100303 G01 I C General.
Inspection Nr: 1522787.015
Citation: 01002
Citation Type: Serious
Abatement Status: Abatement Completed
Initial Penalty: $9,753.00
Current Penalty: $6,827.00
Issuance Date: 08/19/2021
Nr Instances: 4
Nr Exposed: 23
Abatement Date: 08/31/2021
Gravity: 5
Report ID: 1032100
Contest Date:
Final Order: 10/18/2021
Related Event Code (REC):
Emphasis:
Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
---|---|---|---|---|---|---|
Penalty | I: Informal Settlement | 10/18/2021 | $6,827.00 | 08/31/2021 | Serious | |
Penalty | Z: Issued | 08/19/2021 | $9,753.00 | 08/31/2021 | Serious |
Text For Citation: 01 Item/Group: 002 Hazard:
29 CFR 1910.303(g)(1)(i)(C): For electric equipment operating at 600 volts, nominal, or less to ground, and likely to require examination, adjustment, servicing, or maintenance while energized, the width of work space was not clear and did not extend from the grade, floor, or platform to the height required by paragraph (g)(1)(vi) of 29 CFR 1910.303: a) Electrical Room - On or about March 31, 2021, the working space in front of a three-phase 120 volt panel labeled Panel CR-1, had a garbage can and five (5) gallon bucket in front of it, exposing employees to electrical and fire hazards. b) Electrical Room - On or about March 31, 2021, the working space in front of a 480 volt distribution panelboard labeled T1-2-3, had a desk, computer chair, letter storage, and energy control locks and tags in front of it, exposing employees to electrical and fire hazards. c) Electrical Room - On or about March 31, 2021, the working space in front of 240 volt panel labeled WP-2 had a box and garbage can in front of it, exposing employees to electrical and fire hazards. d) Fabrication Shop - On or about March 31, 2021, the working space in front of a breaker panel N had a Smartwasher parts washer in front of it, exposing employees to electrical and fire hazards.