Violation Detail
Standard Cited: 19100119 D03 II Process safety management of highly hazardous chemicals.
Inspection Nr: 1498972.015
Citation: 01002
Citation Type: Serious
Abatement Status: Abatement Completed
Initial Penalty: $8,953.00
Current Penalty: $6,715.00
Issuance Date: 03/25/2021
Nr Instances: 1
Nr Exposed: 6
Abatement Date: 04/15/2021
Gravity: 5
Report ID: 0626600
Contest Date:
Final Order: 04/19/2021
Related Event Code (REC):
Emphasis:
Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
---|---|---|---|---|---|---|
Penalty | I: Informal Settlement | 04/19/2021 | $6,715.00 | 04/15/2021 | Serious | |
Penalty | Z: Issued | 03/25/2021 | $8,953.00 | 04/13/2021 | Serious |
Text For Citation: 01 Item/Group: 002 Hazard:
29 CFR 1910.119(d)(3)(ii):The employer did not document that equipment complies with recognized and generally accepted good engineering practices (RAGAGEP): On or about October 23, 2020, at the at Kinder Morgan Crude & Condensate Park Splitter located in Galena Park, the employer did not document and audit mechanical locking devices on isolation valves used upstream and downstream of pressure relieving devices to verify they remained in the desired position through management practices outlined in ASME Section VIII, Appendix M and Kinder Morgan Procedure No. AP-0917.