Violation Detail
Standard Cited: 19100119 D03 II Process safety management of highly hazardous chemicals.
Inspection Nr: 1480956.015
Citation: 01002
Citation Type: Serious
Abatement Date: 12/28/2020 2
Initial Penalty: $8,193.00
Current Penalty: $8,193.00
Issuance Date: 12/01/2020
Nr Instances: 3
Nr Exposed: 7
Related Event Code (REC):
Gravity: 5
Report ID: 0418300
Contest Date:
Final Order: 01/14/2021
Emphasis:
Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
---|---|---|---|---|---|---|
Penalty | Z: Issued | 12/01/2020 | $8,193.00 | 12/28/2020 | Serious |
Text For Citation: 01 Item/Group: 002 Hazard:
29 CFR 1910.119(d)(3)(ii): The employer did not document that equipment complies with recognized and generally accepted good engineering practices: (a) On or about 07/08/2020 - Engine Room, employees were exposed to ammonia hazards due to the door between the Engine Room and Maintenance Shop would not stay closed, was not tight-fitting, did not swing in the direction of egress to leave the Engine Room, and was not provided with panic-type hardware as specified in International Institute of Ammonia Refrigeration (IIAR) ANS/IIAR 2-2014 section 6.10.2. (b) On or about 07/08/2020 - Engine Room, employees were exposed to ammonia hazards due to the door between the Engine Room and the outside was not provided with panic-type hardware as specified in International Institute of Ammonia Refrigeration (IIAR) ANS/IIAR 2-2014 section 6.10.2. (c) On or about 07/08/2020 - Engine Room, employees were exposed to ammonia hazards due to the Engine Room ammonia detector not activating an alarm that reported to a monitored location as specified in International Institute of Ammonia Refrigeration (IIAR) ANS/IIAR 2-2014 section 6.13.1.2. (d) On or about 07/08/2020 - Ice Box Room, employees were exposed to ammonia hazards due to the Ice Box Room contained refrigeration equipment such as, but not limited to, vessel VS-108 and valve assemblies and did not have an ammonia level 1 detection and alarm as specified in International Institute of Ammonia Refrigeration (IIAR) ANS/IIAR 2-2014 section 7.2.3.