Standard Cited: 19100333 B02 IV B Selection and use of work practices
Inspection Nr: 1378681.015
Citation: 01002
Citation Type: Serious
Abatement Status: Abatement Completed
Initial Penalty: $11,934.00
Current Penalty: $8,353.80
Issuance Date: 05/22/2019
Nr Instances: 1
Nr Exposed: 2
Abatement Date: 07/19/2019
Gravity: 10
Report ID: 0626700
Contest Date:
Final Order: 06/18/2019
Related Event Code (REC):
Emphasis:
| Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
|---|---|---|---|---|---|---|
| Penalty | I: Informal Settlement | 06/18/2019 | $8,353.80 | 07/19/2019 | Serious | |
| Penalty | Z: Issued | 05/22/2019 | $11,934.00 | 06/11/2019 | Serious |
Text For Citation: 01 Item/Group: 002 Hazard:
29 CFR 1910.333(b)(2)(iv)(B): Before circuits or equipment was worked as deenergized, a qualified person did not use test equipment to test the circuit elements and electrical parts of equipment to which employees would be exposed and did not verify that the circuit elements and equipment parts were deenergized: On or about February 6, 2019, building MCC Room A, panel 4E, a qualified person did not verify that the 480 volt panel was deenergized prior to employees attempting to place cables back in the gears.