Violation Detail
Standard Cited: 19100119 D03 I B Process safety management of highly hazardous chemicals.
Inspection Nr: 1307189.015
Citation: 01002
Citation Type: Serious
Abatement Status: Abatement Completed
Initial Penalty: $12,934.00
Current Penalty: $6,467.00
Issuance Date: 08/31/2018
Nr Instances: 3
Nr Exposed: 7
Abatement Date: 09/27/2018
Gravity: 10
Report ID: 1032500
Contest Date:
Final Order: 09/27/2018
Related Event Code (REC):
Emphasis:
Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
---|---|---|---|---|---|---|
Penalty | I: Informal Settlement | 09/27/2018 | $6,467.00 | 09/27/2018 | Serious | |
Penalty | Z: Issued | 08/31/2018 | $12,934.00 | 09/27/2018 | Serious |
Text For Citation: 01 Item/Group: 002 Hazard:
29 CFR 1910.119(d)(3)(i)(B): The employer's piping and instrument diagrams were not accurate and did not represent equipment that was existing and was part of the process. (a) Line B Compressor Room: On or about April 2, 2018 and at times prior, piping and instrument diagrams (P&ID) did not match valves since multiple valves were not labeled. Examples include, but are not limited to no tag on a locked out valve on the high pressure receiver line; condenser drain valve (V1-004) has no tag; and the pressure relief valve (V1-RV1) has a tag with B-5. NOTE: Abatement certification and documentation are required for this item.