Violation Detail
Standard Cited: 19100106 D04 I Flammable liquids.
Inspection Nr: 1281130.015
Citation: 01002
Citation Type: Serious
Abatement Status: Abatement Completed
Initial Penalty: $4,989.00
Current Penalty: $2,993.40
Issuance Date: 04/11/2018
Nr Instances: 1
Nr Exposed: 6
Abatement Date: 05/16/2018
Gravity: 1
Report ID: 0626700
Contest Date:
Final Order: 05/01/2018
Related Event Code (REC):
Emphasis:
| Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
|---|---|---|---|---|---|---|
| Penalty | I: Informal Settlement | 05/01/2018 | $2,993.40 | 05/16/2018 | Serious | |
| Penalty | Z: Issued | 04/11/2018 | $4,989.00 | 05/16/2018 | Serious |
Text For Citation: 01 Item/Group: 002 Hazard:
29 CFR 1910.106(d)(4)(i): Opening(s) from inside flammable and combustible storage room(s) into other rooms or buildings were not provided with noncombustible liquid tight raised seal or ramp at least 4 inches in height and approved self closing fire doors: a) In the mixing room, where the room doors were not approved self closing fire doors and the floor was not raised with a seal or ramp 4 inches in height.