Violation Detail
Standard Cited: 19100303 B02 General.
Inspection Nr: 1259861.015
Citation: 01002
Citation Type: Serious
Abatement Status: Corrected During Inspection
Initial Penalty: $9,234.00
Current Penalty: $5,540.40
Issuance Date: 10/25/2017
Nr Instances: 2
Nr Exposed: 20
Abatement Date:
Gravity: 5
Report ID: 0524200
Contest Date:
Final Order: 11/22/2017
Related Event Code (REC):
Emphasis:
| Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
|---|---|---|---|---|---|---|
| Penalty | I: Informal Settlement | 11/22/2017 | $5,540.40 | Serious | ||
| Penalty | Z: Issued | 10/25/2017 | $9,234.00 | Serious |
Text For Citation: 01 Item/Group: 002 Hazard:
29 CFR 1910.303(b)(2): Listed or labeled electrical equipment was not used or installed in accordance with instructions included in the listing or labeling: a) Decoration Area- On August 25, 2017, the employer failed to ensure that electrical equipment, such as the Square Welded Wall Boxes, was used in accordance with their listing and labeling. These boxes are intended to serve as a wall mounted box and were found to be used as pendant boxes. b) Tray Cutting Area- On August 25, 2017, the employer failed to ensure that electrical equipment, such as the Appleton X Unilet Conduit Outlet Bodies, was used in accordance with their listing and labeling. These bodies are intended to be used as a conduit pathway for turns and runs and not as multi outlet pendants boxes. No abatement certification or documentation is required for this item.