Violation Detail
Standard Cited: 19100106 E03 V A Flammable liquids.
Inspection Nr: 1244436.015
Citation: 01002
Citation Type: Serious
Abatement Status: Abatement Completed
Initial Penalty: $8,873.00
Current Penalty: $5,323.80
Issuance Date: 01/02/2018
Nr Instances: 2
Nr Exposed: 50
Abatement Date: 02/05/2018
Gravity: 10
Report ID: 0213100
Contest Date:
Final Order: 03/20/2018
Related Event Code (REC): C
Emphasis:
Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
---|---|---|---|---|---|---|
Penalty | I: Informal Settlement | 03/20/2018 | $5,323.80 | 02/05/2018 | Serious | |
Penalty | Z: Issued | 01/02/2018 | $8,873.00 | 02/05/2018 | Serious |
Text For Citation: 01 Item/Group: 002 Hazard:
29 CFR 1910.106(e)(3)(v)(a): Areas as defined in paragraph (e)(3)(i) of this section using Category 1 or 2 flammable liquids, or Category 3 flammable liquids with a flashpoint below 100 °F (37.8 °C), was not ventilated at a rate of not less than 1 cubic foot per minute per square foot of solid floor area. This was not accomplished by natural or mechanical ventilation with discharge or exhaust to a safe location outside of the building. Provision was not made for introduction of makeup air in such a manner as not to short circuit the ventilation. Ventilation was not arranged to include all floor areas or pits where flammable vapors may collect: a). On or about 7/3/17, in the ink room, for employees dispensing in dispensing InkCups Ink (category 3 Flammable) into a 1 cup plastic container to add ink to the ink machine. The employees pour the ink from the can into the plastic containers. The InkCups Ink is a category 3 flammable. The employer did not implement ventilation to exhaust to a safe location outside of the building. b). On or about 7/3/17, in the ink room, for the foreman using the Super 16 Paint Gun Cleaner (category 2 Flammable) to clean the ink cups that contain InkCups Ink and thinner on a daily basis. The employer did not implement ventilation to exhaust to a safe location outside of the building.