Violation Detail
Standard Cited: 19100307 C Hazardous (classified) locations.
Inspection Nr: 1239537.015
Citation: 01002
Citation Type: Serious
Abatement Status: Abatement Completed
Initial Penalty: $12,675.00
Current Penalty: $12,675.00
Issuance Date: 12/07/2017
Nr Instances: 1
Nr Exposed: 6
Abatement Date: 08/11/2018
Gravity: 10
Report ID: 0418300
Contest Date: 12/20/2017
Final Order: 08/01/2018
Related Event Code (REC):
Emphasis:
Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
---|---|---|---|---|---|---|
Penalty | J: ALJ Decision | 08/01/2018 | $12,675.00 | 08/11/2018 | Serious | |
Penalty | C: Contested | 02/06/2018 | $12,675.00 | 01/04/2018 | Serious | |
Penalty | Z: Issued | 12/07/2017 | $12,675.00 | 01/04/2018 | Serious |
Text For Citation: 01 Item/Group: 002 Hazard:
29 CFR 1910.307(c): Equipment, wiring methods, and installations of equipment in hazardous (classified) locations were not intrinsically safe, approved for the hazardous (classified) location, or safe for the hazardous (classified) location: (a) On or about 6/12/2017 - Express Lube Pit, electrical receptacles, a pedestal fan, and a Hessaire Portable Evaporative Cooler, Model MC37, were not intrinsically safe for use in a Class I, Division 1 location created as a result of employees using flammable brake wash liquid to clean oil and grease from the service pit floor, thereby exposing employees to a flash fire and explosion hazard from the aforementioned ignition sources.