Violation Detail
Standard Cited: 19100119 D03 I B Process safety management of highly hazardous chemicals.
Inspection Nr: 1203878.015
Citation: 01002
Citation Type: Serious
Abatement Date: 08/02/2017 2
Initial Penalty: $12,675.00
Current Penalty: $7,462.00
Issuance Date: 07/14/2017
Nr Instances: 5
Nr Exposed: 4
Related Event Code (REC):
Gravity: 10
Report ID: 0626000
Contest Date:
Final Order: 08/07/2017
Emphasis:
Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
---|---|---|---|---|---|---|
Penalty | I: Informal Settlement | 08/07/2017 | $7,462.00 | 08/02/2017 | Serious | |
Penalty | Z: Issued | 07/14/2017 | $12,675.00 | 08/02/2017 | Serious |
Text For Citation: 01 Item/Group: 002 Hazard:
29 CFR 1910.119(d)(3)(i)(B): The employer's piping and instrument diagrams (P&ID) were not accurate. On or about 01/17/2017, at the Eddy Packing Inc. facility located in Yoakum Texas, the employer did not ensure that piping and instrument diagrams (P&IDs) were accurate. The P&IDs were not accurate as the following but not limited to. a. EDDYPACK-P&ID01, Rev. #4 (Engine Room) and EDDYPACK-P&ID02, Rev. #3 (Engine Room). These P&IDs did not include a third vent/stack line (yellow one) for anhydrous ammonia. b. EDDYPACK-P&ID04, Rev. #2 (Evaporators). The Evaporators EV-14 and EV-15 located in a boning room must be removed per management of changes (MOCs) MCF#006 and MCF#005 in August and September 2015 respectively. c. EDDYPACK-P&ID06, Rev. #1 (Evaporators). The Evaporator EV-19 located in a chill room must be removed. d. EDDYPACK-P&ID07, Rev. #1 (Evaporators). The Evaporator EV-30 located in a sausage holding cooler must be removed. e. EDDYPACK-P&ID09, Rev. #3 (Evaporators - 2006 Expansion). Pipelines are undefined. f. EDDYPACK-P&ID14, Rev. # 1(Evaporators). The Evaporator EV-89 located in a locker room must be removed per management of change MCF#004 in October 2015.