Violation Detail
Standard Cited: 19100119 D03 III Process safety management of highly hazardous chemicals.
Inspection Nr: 1183840.015
Citation: 01002
Citation Type: Serious
Abatement Status: Abatement Completed
Initial Penalty: $12,675.00
Current Penalty: $6,200.00
Issuance Date: 04/11/2017
Nr Instances: 3
Nr Exposed: 2
Abatement Date: 04/26/2017
Gravity: 10
Report ID: 0627700
Contest Date:
Final Order: 10/10/2017
Related Event Code (REC):
Emphasis:
Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
---|---|---|---|---|---|---|
Penalty | I: Informal Settlement | 10/10/2017 | $6,200.00 | 04/26/2017 | Serious | |
Penalty | Z: Issued | 04/11/2017 | $12,675.00 | 04/26/2017 | Serious |
Text For Citation: 01 Item/Group: 002 Hazard:
29 CFR 1910.119(d)(3)(iii): For existing equipment designed and constructed in accordance with codes, standards, or practices no longer in general use, the employer did not determine and document that the equipment in the process was designed, maintained, inspected, tested, and operating in a safe manner: a) This violation was most recently observed on or about October 14, 2016 and times prior thereto, the north refrigeration room at OK Foods located in Oklahoma City, Oklahoma contains gas-fired boilers in the same area as the ammonia refrigeration equipment. b) This violation was most recently observed on or about October 14, 2016 and times prior thereto, the ammonia detectors in the north refrigeration room at OK Foods located in Oklahoma City, Oklahoma were not operable.