Violation Detail
Standard Cited: 19100119 E03 I Process safety management of highly hazardous chemicals.
Inspection Nr: 1157732.015
Citation: 01002
Citation Type: Serious
Abatement Status: Abatement Completed
Initial Penalty: $7,572.00
Current Penalty: $6,000.00
Issuance Date: 12/16/2016
Nr Instances: 5
Nr Exposed: 20
Abatement Date: 01/20/2017
Gravity: 5
Report ID: 0213100
Contest Date:
Final Order: 01/13/2017
Related Event Code (REC):
Emphasis:
Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
---|---|---|---|---|---|---|
Penalty | I: Informal Settlement | 01/13/2017 | $6,000.00 | 01/20/2017 | Serious | |
Penalty | Z: Issued | 12/16/2016 | $7,572.00 | 01/20/2017 | Serious |
Text For Citation: 01 Item/Group: 002 Hazard:
29 CFR 1910.119(e)(3)(i): The process hazard analysis did not address the hazards of the process. (a) Anhydrous ammonia refrigeration process (various locations): On or prior 6/23/16, The process hazard analysis did not address hazards associated with support and protection of 1/2" diameter HPL lines for process equipment including but not limited to: PT silos, Raw silos, Hansen Auto Purger AP-1, Transfer Assembly with Teikoku pump TA2, Ice Cream Freezer APV-WS-308, Coolmatic AH-1, and New King Unit KU-1. (b) Anhydrous ammonia refrigeration process, North Engine room: On or prior to 6/23/16, the process hazard analysis did not address hazards associated with operation of the Suction Accumulator SA2 at a temperature of -35F, which is below the MDMT for the vessel.